On Wednesday 13 August 2003 18:45, foxprints2003 wrote:
MIN_LIMIT_SWITCH_POLARITY = <0 or 1>
If it's 0 make it one, if it's 1, make it 0. Your problem will be fixed, and
you can go on to the next one... ;)
Matt
> I have just begun testing a new gantry system & I have run into aGo down to the [AXIS_2] section and look for the line that says:
> problem with EMC.
> I have a 3 axis servo system with run by EMC with an 8 axis model 2
> Servo-To-Go board. On EMC startup the Z axis coordinate display is
> red & I get an error message "Minimum Hardware Limit on axis 2
> exceeded"
MIN_LIMIT_SWITCH_POLARITY = <0 or 1>
If it's 0 make it one, if it's 1, make it 0. Your problem will be fixed, and
you can go on to the next one... ;)
Matt