The diode is there to reduce radiated electrical noise that the relay
will generate when turned off. This transient can be very intense and
is best handled at the source, thus the diode.
AC relays due to the nature of AC power have to have a solution other
than a diode. Often RC networks and or metal oxide varistors are used
here. Both of these devices could also be found across a DC relay also
to supplement the diode. The diode though is the primary protection
mechanism.
One thing to be aware of is that the diodes will change the time
constant of the circuit. This is important in some usages.
Dave
The diode is there to reduce radiated electrical noise that the relay
will generate when turned off. This transient can be very intense and
is best handled at the source, thus the diode.
AC relays due to the nature of AC power have to have a solution other
than a diode. Often RC networks and or metal oxide varistors are used
here. Both of these devices could also be found across a DC relay also
to supplement the diode. The diode though is the primary protection
mechanism.
One thing to be aware of is that the diodes will change the time
constant of the circuit. This is important in some usages.
Dave
On Sat, 2004-01-10 at 21:05, washcomp wrote:
> Back when I was a kid learning about relay circuits on the job
> (1960's), most of the control circuits I got involved in used low
> voltage A.C. and I don't ever remember seeing a diode. I just found
> out that it's good practice to put a diode across the coil of relays
> to keep them from chattering due to the current stored in the coil
> inductance. Question is: Only on D.C. relays or is this supposed
> to be done on A.C. relays as well?
>
> Jeff
>
>
>
>
> Addresses:
> FAQ: http://www.ktmarketing.com/faq.html
> FILES: http://groups.yahoo.com/group/CAD_CAM_EDM_DRO/files/
> Post Messages: CAD_CAM_EDM_DRO@yahoogroups.com
>
> Subscribe: CAD_CAM_EDM_DRO-subscribe@yahoogroups.com
> Unsubscribe: CAD_CAM_EDM_DRO-unsubscribe@yahoogroups.com
> List owner: CAD_CAM_EDM_DRO-owner@yahoogroups.com, wanliker@..., timg@...
> Moderator: pentam@... indigo_red@... davemucha@... [Moderators]
> URL to this group: http://groups.yahoo.com/group/CAD_CAM_EDM_DRO
>
> OFF Topic POSTS: General Machining
> If you wish to post on unlimited OT subjects goto: aol://5863:126/rec.crafts.metalworking or go thru Google.com to reach it if you have trouble.
> http://www.metalworking.com/news_servers.html
>
> http://groups.yahoo.com/group/jobshophomeshop I consider this to be a sister site to the CCED group, as many of the same members are there, for OT subjects, that are not allowed on the CCED list.
>
> NOTICE: ALL POSTINGS TO THIS GROUP BECOME PUBLIC DOMAIN BY POSTING THEM. DON'T POST IF YOU CAN NOT ACCEPT THIS.....NO EXCEPTIONS........
> bill
> List Mom
> List Owner
>
>
>
> Yahoo! Groups Links
>
> To visit your group on the web, go to:
> http://groups.yahoo.com/group/CAD_CAM_EDM_DRO/
>
> To unsubscribe from this group, send an email to:
> CAD_CAM_EDM_DRO-unsubscribe@yahoogroups.com
>
> Your use of Yahoo! Groups is subject to:
> http://docs.yahoo.com/info/terms/
>
>
>
Discussion Thread
washcomp
2004-01-10 18:05:55 UTC
Relay question about diodes across the coil
Dave Fisher
2004-01-10 18:20:23 UTC
RE: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Greg Jackson
2004-01-10 18:35:09 UTC
RE: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Jeff Goldberg
2004-01-10 18:40:34 UTC
RE: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
archie & kathy
2004-01-10 19:44:28 UTC
Re: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Harvey White
2004-01-10 19:45:38 UTC
Re: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
JanRwl@A...
2004-01-10 19:56:50 UTC
Re: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Harvey White
2004-01-10 20:05:19 UTC
Re: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Jon Elson
2004-01-10 20:18:23 UTC
Re: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Jeff Goldberg
2004-01-10 20:39:19 UTC
RE: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Jeff Goldberg
2004-01-10 20:42:51 UTC
RE: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Jeff Goldberg
2004-01-10 20:46:40 UTC
RE: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Jeff Goldberg
2004-01-10 20:53:47 UTC
RE: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Harvey White
2004-01-10 21:24:23 UTC
Re: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Harvey White
2004-01-10 21:27:04 UTC
Re: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Paul Davis
2004-01-10 21:37:09 UTC
RE: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
David A. Frantz
2004-01-11 02:33:13 UTC
Re: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Jon Elson
2004-01-11 14:16:55 UTC
Re: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Jon Elson
2004-01-11 14:19:07 UTC
Re: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Paul Davis
2004-01-11 17:22:40 UTC
Re: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
Jon Elson
2004-01-11 19:44:20 UTC
Re: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
washcomp
2004-01-11 20:06:18 UTC
Re: Relay question about diodes across the coil
JanRwl@A...
2004-01-11 20:28:29 UTC
Re: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil
David A. Frantz
2004-01-12 11:24:51 UTC
Re: [CAD_CAM_EDM_DRO] Relay question about diodes across the coil