Furthermore, if the fuse was a 'quick-blow' type, the
inrush current to the x-former might've tripped it.

RayHex

----------
> From: Jon Elson <elson@...>
>snip>
> What is the rating of the fuse that blew? Is it on the
AC input to the
> transformer? Full load is roughly 1200 W, which would
draw 10 A if
> the power factor was perfect. Since it won't be anywhere
near perfect,
> a full load on such a power supply may cause an RMS
current draw
> that could even exceed 15 A.