Tim Goldstein wrote:
phase motors that I have use the same numbering scheme;
If you measure low ohms between 7-8-9 this is good. This is the first
winding, permanently connected in a wye.
Join 4-5-6 this is the center of the second wye.
Connect your 3 phase line to the pairs; 1-7, 2-8, 3-9
Good luck.
_________________________________________________________________
Get your FREE download of MSN Explorer at http://explorer.msn.com/intl.asp
>I just got a 3 phase Setco 6103 3 phase spindle and I am trying to figureTim, Check the wires out carefully for numbers printed on them. All the 3
>out how to hook it up. It is rated as 230/460v 3phase. When I look at the
>wires coming out of the motor into the junction box there are 2 bundles.
>One
>has 5 wires and the other has 4. Anyone have any idea how I hook this up
>for
>230 v usage?
phase motors that I have use the same numbering scheme;
If you measure low ohms between 7-8-9 this is good. This is the first
winding, permanently connected in a wye.
Join 4-5-6 this is the center of the second wye.
Connect your 3 phase line to the pairs; 1-7, 2-8, 3-9
Good luck.