Jon Anderson wrote:

> Picked up a couple 15 amp 3ph line filters yesterday at a surplus
> outlet. Units are mfg. by SAE Power, looked at their web site last night
> and the units they show for 3ph have a neutral and ground connection
> in addition to the three powered lines. This unit has only the power
> connections. It's marked with what looks like a Varian P/N, and doesn't
> look like the off-the-shelf units SAE lists on the web site. Probably a
> custom unit. Would like to know if I will run into any trouble if my
> ground wire isn't filtered.

The ground wire should not be filtered. that can be a safety hazard. The
case of the filter needs to be grounded, however, or it won't do any good.
What do you intend to use them for?

Jon

Discussion Thread

Jon Anderson 2001-08-16 07:47:29 UTC Question, 3ph line filter Jon Elson 2001-08-16 10:45:24 UTC Re: [CAD_CAM_EDM_DRO] Question, 3ph line filter Jon Anderson 2001-08-16 12:24:12 UTC Re: [CAD_CAM_EDM_DRO] Question, 3ph line filter Jon Elson 2001-08-16 20:53:44 UTC Re: [CAD_CAM_EDM_DRO] Question, 3ph line filter Jon Anderson 2001-08-16 21:06:14 UTC Re: [CAD_CAM_EDM_DRO] Question, 3ph line filter Jon Elson 2001-08-16 23:00:12 UTC Re: [CAD_CAM_EDM_DRO] Question, 3ph line filter Jon Anderson 2001-08-16 23:17:02 UTC Re: [CAD_CAM_EDM_DRO] Question, 3ph line filter