Re: current rating of transformers

on 2004-10-24 09:42:30 UTC
--- In CAD_CAM_EDM_DRO@yahoogroups.com, Jon Elson <elson@p...> wrote:
> turbulatordude wrote:
>
> >Hi,
> >
> >If I have a 24 volt, (12V-0-12) center tap transformer like the
MPJA
> >unit.
> >http://www.mpja.com/productview.asp?product=7846+TR
> >
> >And isolate the center tap I get 24 volts.
> >
> >But when rectified, doesn't the current change also ?
> >
> >There is a note in the catalogue that for this wiring the amps are
> >1.8x
> >
> >The catalogue refers to required ouput amps
> >
> >
> >full wave bridge cap input filter 1.8x to required output amps
> >full wave choke input filter = required output amps
> >full wave, center tap, cap = 1.2x roa
> >full wave, center tap, choke = 0.7x roa
> >
> >
> Using the full winding means current flows in both ends of the
winding
> all the time. So, the current rating must go down. With full-wave
> center tap, each half of the winding gets a rest 50% of the time, so
> current rating goes up. I guess what they are saying here is that
you
> take the load current and multiply by these factors to get the
rating
> of the transformer.
>
> Jon


This is where I'm confused.

If I use the full winding, 24 volts, do I really get 5.8 amps ?
and with center tap, 12 volts, 8 amps
but using a choke at 24 volts, I can get the full 10 amps ?

I wish they would have said secondary output x (factor) = available
ouput.

Dave

Discussion Thread

turbulatordude 2004-10-24 08:57:44 UTC current rating of transformers Jon Elson 2004-10-24 09:25:05 UTC Re: [CAD_CAM_EDM_DRO] current rating of transformers turbulatordude 2004-10-24 09:42:30 UTC Re: current rating of transformers Andy Wander 2004-10-24 11:14:03 UTC RE: [CAD_CAM_EDM_DRO] current rating of transformers Jon Elson 2004-10-24 20:03:42 UTC Re: [CAD_CAM_EDM_DRO] Re: current rating of transformers Jon Elson 2004-10-24 20:28:24 UTC Re: [CAD_CAM_EDM_DRO] current rating of transformers learnningstuff 2004-10-24 23:05:59 UTC Re: current rating of transformers turbulatordude 2004-10-24 23:30:59 UTC Re: current rating of transformers Andy Wander 2004-10-25 05:12:26 UTC RE: [CAD_CAM_EDM_DRO] current rating of transformers Andy Wander 2004-10-25 05:22:39 UTC RE: [CAD_CAM_EDM_DRO] Re: current rating of transformers turbulatordude 2004-10-25 09:47:02 UTC Re: current rating of transformers Jon Elson 2004-10-25 10:15:38 UTC Re: [CAD_CAM_EDM_DRO] current rating of transformers Andy Wander 2004-10-25 10:45:06 UTC RE: [CAD_CAM_EDM_DRO] current rating of transformers turbulatordude 2004-10-25 11:28:34 UTC Re: current rating of transformers John Dammeyer 2004-10-25 11:46:56 UTC RE: [CAD_CAM_EDM_DRO] current rating of transformers kmslinda 2004-10-25 14:40:53 UTC Re: current rating of transformers Jon Elson 2004-10-25 22:59:28 UTC Re: [CAD_CAM_EDM_DRO] Re: current rating of transformers turbulatordude 2004-10-25 23:27:20 UTC Re: current rating of transformers caudlet 2004-10-26 07:02:12 UTC Re: current rating of transformers Fred Smith 2004-10-26 07:19:04 UTC Re: current rating of transformers Jon Elson 2004-10-26 09:18:02 UTC Re: [CAD_CAM_EDM_DRO] Re: current rating of transformers Stephen Wille Padnos 2004-10-26 11:47:51 UTC Re: [CAD_CAM_EDM_DRO] Re: current rating of transformers Bloy2004 2004-10-26 14:51:36 UTC Re: current rating of transformers Bloy2004 2004-10-26 18:57:13 UTC Re: current rating of transformers Jon Elson 2004-10-26 23:07:20 UTC Re: [CAD_CAM_EDM_DRO] Re: current rating of transformers Bloy2004 2004-10-27 06:14:34 UTC Re: current rating of transformers Roy J. Tellason 2004-10-27 10:11:48 UTC Re: [CAD_CAM_EDM_DRO] Re: current rating of transformers Jon Elson 2004-10-27 10:36:31 UTC Re: [CAD_CAM_EDM_DRO] Re: current rating of transformers