Art Fenerty wrote:

> You guys might wanta take note that the new Gekko 210's require that the DIR
> signal stay in the proper polarity for up to 100uS after the step pulse. You
> don't have to lead the step pulse, but you MUST lag it by up to 60-100uS. I
> have just revised the Master5 release edition to take this into account. I
> suddenly had two customers who could only get one direction after upgrading
> to Gekko 210's. Nice controller though. I taked to Marris about the problem,
> and the obvious solution was to leave the dir pulse set until next pulse
> time.

I had some trouble getting through to the Gecko pages, but what I did read
showed only a 20 uS hold after the step pulse, not 100 uS. I was able to check 3
of the 4 models data sheets, including the G210.

Jon

Discussion Thread

Cryo 2001-05-08 11:57:31 UTC EMC signal output Jon Elson 2001-05-08 13:21:15 UTC Re: [CAD_CAM_EDM_DRO] EMC signal output Art Fenerty 2001-05-08 14:03:11 UTC Re: [CAD_CAM_EDM_DRO] EMC signal output Tim Goldstein 2001-05-08 14:08:07 UTC RE: [CAD_CAM_EDM_DRO] EMC signal output Jon Elson 2001-05-08 15:54:58 UTC Re: [CAD_CAM_EDM_DRO] EMC signal output Jon Elson 2001-05-08 23:33:01 UTC Re: [CAD_CAM_EDM_DRO] EMC signal output Jon Elson 2001-05-08 23:39:23 UTC Re: [CAD_CAM_EDM_DRO] EMC signal output Cryo 2001-05-09 05:17:59 UTC Re[2]: [CAD_CAM_EDM_DRO] EMC signal output Jon Elson 2001-05-09 08:26:49 UTC Re: [CAD_CAM_EDM_DRO] EMC signal output Tim Goldstein 2001-05-09 09:08:21 UTC RE: [CAD_CAM_EDM_DRO] EMC signal output ballendo@y... 2001-05-10 03:29:20 UTC Re: EMC signal output Jon Elson 2001-05-13 23:26:16 UTC Re: [CAD_CAM_EDM_DRO] EMC signal output