Re: [CAD_CAM_EDM_DRO] EMC signal output
Posted by
Art Fenerty
on 2001-05-08 14:03:11 UTC
You guys might wanta take note that the new Gekko 210's require that the DIR
signal stay in the proper polarity for up to 100uS after the step pulse. You
don't have to lead the step pulse, but you MUST lag it by up to 60-100uS. I
have just revised the Master5 release edition to take this into account. I
suddenly had two customers who could only get one direction after upgrading
to Gekko 210's. Nice controller though. I taked to Marris about the problem,
and the obvious solution was to leave the dir pulse set until next pulse
time.
Art
signal stay in the proper polarity for up to 100uS after the step pulse. You
don't have to lead the step pulse, but you MUST lag it by up to 60-100uS. I
have just revised the Master5 release edition to take this into account. I
suddenly had two customers who could only get one direction after upgrading
to Gekko 210's. Nice controller though. I taked to Marris about the problem,
and the obvious solution was to leave the dir pulse set until next pulse
time.
Art
Discussion Thread
Cryo
2001-05-08 11:57:31 UTC
EMC signal output
Jon Elson
2001-05-08 13:21:15 UTC
Re: [CAD_CAM_EDM_DRO] EMC signal output
Art Fenerty
2001-05-08 14:03:11 UTC
Re: [CAD_CAM_EDM_DRO] EMC signal output
Tim Goldstein
2001-05-08 14:08:07 UTC
RE: [CAD_CAM_EDM_DRO] EMC signal output
Jon Elson
2001-05-08 15:54:58 UTC
Re: [CAD_CAM_EDM_DRO] EMC signal output
Jon Elson
2001-05-08 23:33:01 UTC
Re: [CAD_CAM_EDM_DRO] EMC signal output
Jon Elson
2001-05-08 23:39:23 UTC
Re: [CAD_CAM_EDM_DRO] EMC signal output
Cryo
2001-05-09 05:17:59 UTC
Re[2]: [CAD_CAM_EDM_DRO] EMC signal output
Jon Elson
2001-05-09 08:26:49 UTC
Re: [CAD_CAM_EDM_DRO] EMC signal output
Tim Goldstein
2001-05-09 09:08:21 UTC
RE: [CAD_CAM_EDM_DRO] EMC signal output
ballendo@y...
2001-05-10 03:29:20 UTC
Re: EMC signal output
Jon Elson
2001-05-13 23:26:16 UTC
Re: [CAD_CAM_EDM_DRO] EMC signal output