blueveil@... wrote:

> I have got a lot of good thoughts from the users in the group.
> Thanks for all your answers. Here is one more question on the
> 220 single phase cnc.
> I just looked at the cnc main box and the motors. They are listed
> at 220 or 230 or 240 at 50/60 hz.
> Does this make a difference? Maybe I could just plug it into a
> step-up transformer here in the U.S. to see if it runs.

In the US, most '220' service delivers 240+ volts to the house.
Measure it, and you will see it is definitely on the high side.
Most equipment rated at 220 have the capability to run from
240 V without harm. Equipment rated strictly for 208 V may
not, however. If you have voltage adjusting jumpers, you can
set it for 240 V and it should extend the life of the equipment.

Jon

Discussion Thread

blueveil@e... 2001-05-16 10:14:17 UTC U.S. 220 vs Euro 220 wanliker@a... 2001-05-16 10:59:37 UTC Re: [CAD_CAM_EDM_DRO] U.S. 220 vs Euro 220 Carol & Jerry Jankura 2001-05-16 13:01:23 UTC RE: [CAD_CAM_EDM_DRO] U.S. 220 vs Euro 220 stevesng@n... 2001-05-16 16:32:42 UTC Re: U.S. 220 vs Euro 220 JanRwl@A... 2001-05-16 17:27:06 UTC Re: [CAD_CAM_EDM_DRO] U.S. 220 vs Euro 220 A. G. Eckstein 2001-05-16 17:45:07 UTC Re: [CAD_CAM_EDM_DRO] U.S. 220 vs Euro 220 info.host@b... 2001-05-17 05:08:15 UTC Re: [CAD_CAM_EDM_DRO] U.S. 220 vs Euro 220 machines@n... 2001-05-17 05:36:32 UTC Re: U.S. 220 vs Euro 220 info.host@b... 2001-05-17 11:56:44 UTC Re: [CAD_CAM_EDM_DRO] Re: U.S. 220 vs Euro 220 Sven Peter, TAD S.A. 2001-05-17 12:10:22 UTC Re: [CAD_CAM_EDM_DRO] U.S. 220 vs Euro 220 blueveil@e... 2001-05-17 12:18:10 UTC Re: U.S. 220 vs Euro 220 Carol & Jerry Jankura 2001-05-17 13:03:59 UTC RE: [CAD_CAM_EDM_DRO] U.S. 220 vs Euro 220 Sven Peter, TAD S.A. 2001-05-17 13:09:10 UTC Re: [CAD_CAM_EDM_DRO] U.S. 220 vs Euro 220 Sven Peter, TAD S.A. 2001-05-17 13:11:34 UTC Re: [CAD_CAM_EDM_DRO] Re: U.S. 220 vs Euro 220 Carol & Jerry Jankura 2001-05-17 13:38:58 UTC RE: [CAD_CAM_EDM_DRO] U.S. 220 vs Euro 220 Jon Elson 2001-05-17 14:08:52 UTC Re: [CAD_CAM_EDM_DRO] Re: U.S. 220 vs Euro 220 Jon Elson 2001-05-17 14:46:54 UTC Re: [CAD_CAM_EDM_DRO] Re: U.S. 220 vs Euro 220 wanliker@a... 2001-05-17 15:26:56 UTC Re: [CAD_CAM_EDM_DRO] Re: U.S. 220 vs Euro 220 Sven Peter, TAD S.A. 2001-05-17 17:04:58 UTC Re: [CAD_CAM_EDM_DRO] U.S. 220 vs Euro 220 JanRwl@A... 2001-05-18 19:55:09 UTC Re: [CAD_CAM_EDM_DRO] Re: U.S. 220 vs Euro 220 ballendo@y... 2001-05-21 18:17:47 UTC Re: U.S. 220 vs Euro 220 Ward M. 2001-05-21 23:43:29 UTC RE: [CAD_CAM_EDM_DRO] Re: U.S. 220 vs Euro 220